Page 221 - Andersen Architectural Collection A-Series 2018-19 Product Guide for Professionals
P. 221
TECHNICAL DATA
PREFORMANCE STANDARDS HALLMARK CERTIFICATION Performance Grade, Air Infiltration and Sound Transmission Ratings — A-Series Windows and Patio Doors
The Window and Door Manufacturers Association (WDMA), the American Architectural The Window and Door Manufacturers Association (WDMA) sponsored Hallmark Certification For current performance information please visit andersenwindows.com.
Manufacturers Association (AAMA) and the Canadian Standards Association (CSA) jointly release Program provides manufacturers with certification to the AAMA/WDMA/CSA 101/I.S.2/A440-11 Standard Standard Glass
the North American Fenestration Standard/Specification for Windows, Doors and Skylights Standard and is designed to provide builders, architects, specifiers and consumers with an Glass AAMA/WDMA/CSA 101/IS2/A440 +/- Corresponding Glass Sound Outdoor/Indoor Air Infiltration
Transmission
Transmission
®
(NAFS-11) where "-11" refers to the most recent publication year of 2011. NAFS is also referred to easily recognizable means of identifying products that have been manufactured and tested Andersen Product Construction Performance Grade (PG) Design Pressure (DP) Class (STC) Class (OITC) CFM/FT 2
as AAMA/WDMA/CSA 101/I.S.2/A440, which is how the International Code Council (ICC) lists this in accordance with NAFS (AAMA/WDMA/CSA 101/I.S.2/A440) industry standards and other Dual-Pane 50/50 27 23 < 0.2
standard in the 2012 and 2015 International Residential Code (IRC) and International Building applicable performance standards. Conformance is determined by periodic in-plant Casement Windows Triple-Pane Class LC-PG50 Size Tested 47" x 95" 50/50 30 25 < 0.2
Code (IBC) as the means to indicate the window, door or skylights design pressure rating used to inspections by a third-party administrator. Inspections include auditing licensee quality Dual-Pane 50/50 28 22 < 0.2
determine compliance to the jobsite design pressure requirements. control procedures and processes and a review to confirm products are manufactured in Awning Windows Class LC-PG50 Size Tested 71" x 47"
Triple-Pane 50/50 29 23 < 0.2
A product only achieves a “Performance Grade” or “PG” rating when it complies with all of the accordance with the appropriate performance standards. Periodic testing of representative Dual-Pane 50/50 27 22 < 0.2
NAFS performance requirements such as ease of operation, air infiltration resistance, resistance to product constructions and components by an independent testing laboratory is also required. Double-Hung Windows Triple-Pane Class LC-PG50 Size Tested 47" x 95" 50/50 28 23 < 0.2
water penetration and resistance to forced entry, etc. A “Design Pressure Rating” or “DP” rating When all of the program requirements are met, the licensee is authorized to use the
only depicts the design and structural load performance. WDMA Hallmark registered logo on their Certification Label as a means of identifying Picture Windows Dual-Pane Class LC-PG50 Size Tested 71" x 95" 50/50 27 22 < 0.2
Performance Classes products and their performance ratings. Triple-Pane 50/50 30 25 < 0.2
The NAFS Standard/Specification defines requirements for four performance classes. Performance Products successfully obtaining Hallmark Certification will be labeled with a 3-part code, Stationary Transom Windows Dual-Pane Class LC-PG50 Size Tested 71" x 39" 50/50 27 22 < 0.2
classes are designated R, LC, CW and AW. This classification system provides for several levels which includes performance class, performance grade and size tested. In addition to this Triple-Pane 50/50 31 24 < 0.2
of performance. Product selection is always based on the performance and building code mandatory requirement, you are allowed to list the design pressure on a separate line. Dual-Pane 50/50 28 22 < 0.2
requirements of the particular project. Fixed Transom Windows Triple-Pane Class LC-PG50 Size Tested 71" x 35" 50/50 28 23 < 0.2
Elements of Performance Grade (PG) Designations Direct-Set Specialty Windows
In order to qualify for a given performance grade (PG), test specimens need to pass all required Andersen Corporation Rectangular Dual-Pane Class LC-PG50 Size Tested 125" x 84" 50/50 28 24 < 0.2
A-SERIES CASEMENT WINDOW
performance tests for the following, in addition to all required auxiliary (durability) and applicable Hallmark Certified Manufacturer stipulates certification as indicated below. Arch Dual-Pane Class LC-PG50 Size Tested 125" x 84" 50/50 28 24 < 0.2
material/component tests (not shown here) for the applicable product type and desired www.wdma.com
performance class: STANDARD RATING Springline ™ Dual-Pane Class LC-PG50 Size Tested 125" x 84" 50/50 28 24 < 0.2
CLASS LC (1) – PG50 (2) – SIZE TESTED 35.3 X 71.3 in. (3)
(a) Operating force (if applicable): Maximum operating force varies by product type and AAMA/WDMA/CSA 101/I.S.2/A440-11 DP+50/-50 (4) Sash-Set Specialty Windows
performance class. AAMA/WDMA/CSA 101/I.S.2/A440-08 CLASS LC (1) – PG50 (2) – SIZE TESTED 35.3 X 71.3 in. (3) Rectangular Dual-Pane Class LC-PG50 Size Tested 125" x 75" 50/50 29 24 < 0.2
(b) Air leakage resistance: Tested in accordance with ASTM E283 at a test pressure of 1.57 psf. DP+50/-50 (4) Springline ™ Dual-Pane Class LC-PG50 Size Tested 125" x 75" 50/50 29 24 < 0.2
Allowable air infiltration for R, LC and CW class designations is 0.3 cubic feet per minute per Arch Dual-Pane Class LC-PG50 Size Tested 125" x 75" 50/50 29 24 < 0.2
square foot of frame (cfm/ft ). (1) – Performance Class Complementary Casement Windows
2
(c) Water penetration resistance: Tested in accordance with ASTM E547 with the specified test (2) – Performance Grade Casement (venting) Dual-Pane Class LC-PG50 Size Tested 35" x 84" 50/50 † † < 0.2
pressure applied per NAFS-11. Test consists of four cycles. Each cycle consists of five minutes (3) – Size Tested
with pressure applied and one minute with the pressure released, during which the water spray is (4) – Design Pressure Casement (stationary) Dual-Pane Class LC-PG60 Size Tested 120" x 78" 60/60 † † < 0.2
continuously applied. Water spray shall be uniformly applied at a constant rate of 5 U.S. gal/ft • hr. In the example above, the performance class is LC, the performance grade (PG) is 50 pounds French Casement (venting) Dual-Pane Class LC-PG30 Size Tested 56" x 72" 30/30 † † < 0.2
2
(d) Uniform load deflection test: Tested in accordance with ASTM E330 for both positive per square foot (psf) and the size tested is 35.3" x 71.3". What this means to the specifier Frenchwood ® Gliding Patio Door
and negative pressure (pressure defined by NAFS-11) with the load maintained for a period of is, based on the performance grade chart, the laboratory tested air infiltration was less Single Stationary (611, 80, 100) Dual-Pane Class LC-PG45 Size Tested 50" x 119" 45/45 30 25 < 0.2
10 seconds. The test specimen shall be evaluated for deflection during each load, for permanent than 0.3 cfm/ft (test pressure is always 1.57 psf and the allowable airflow is 0.3 cfm/ft ), Single Stationary (611, 80) Triple-Pane Class LC-PG45 Size Tested 50" x 95" 45/45 32 28 < 0.3
2
2
damage after each load and for any effects on the normal operation of the specimen. Starting the product tested successfully resisted a laboratory water penetration test at a test Single Stationary, PG Upgrade (611, 80) Dual-Pane Class LC-PG65 Size Tested 50" x 95" 65/80 30 25 < 0.2
with the 2008 version of NAFS, design pressure (DP) will only represent the "uniform load pressure of 7.5 psf, the product tested successfully withstood a laboratory positive test Single Stationary, PG Upgrade (100) Dual-Pane Class LC-PG55 Size Tested 50" x 119" 55/55 30 25 < 0.2
deflection test". pressure of 75 psf, a laboratory negative test pressure of 75 psf and the product tested
(e) Uniform load structural test: Tested in accordance with ASTM E330 for both positive and passed the laboratory requirements for operational force and forced entry resistance. Based Two-Panel (611, 80) Dual-Pane Class LC-PG50 Size Tested 95" x 95" 50/50 30 25 < 0.2
negative pressure (pressure defined by NAFS-11) with the load maintained for a period of 10 on this test, all products smaller in both width and height can be labeled with this product Triple-Pane 50/50 29 25 < 0.2
seconds. After loads are removed, there shall be no permanent deformation in excess of 0.4% performance rating. Two-Panel (100) Dual-Pane Class LC-PG45 Size Tested 95" x 119" 45/45 29 25 < 0.2
of its span and no damage to the unit, which would make it inoperable. Two-Panel, PG Upgrade (611) Dual-Pane Class LC-PG70 Size Tested 95" x 82" 70/80 † † < 0.2
(f) Forced-entry resistance (if applicable): Tested in accordance with ASTM F588 (windows), IMPORTANT Two-Panel, PG Upgrade (80, 100) Dual-Pane Class LC-PG55 Size Tested 95" x 119" 55/55 † † < 0.2
F476 (swinging doors) and F842 (sliding doors) at a performance level 10 rating.
Building codes prescribe design pressure based on a variety of criteria (i.e. windspeed Three-Panel (611) Dual-Pane Class LC-PG50 Size Tested 141" x 82" 50/50 † † < 0.2
Performance Grades (PG) & Corresponding Test Pressures (psf) zone, building height, building type, jobsite exposure, etc.). Design pressures derived from Three-Panel, PG Upgrade (611) Dual-Pane Class LC-PG65 Size Tested 141" x 82" 65/70 † † < 0.2
Performance Maximum Performance Grade (PG) test requirements should be used to determine compliance to Three-Panel (80, 100) Dual-Pane Class LC-PG40 Size Tested 141" x 119" 40/40 † † < 0.2
Class/ Air Infiltration Allowable Air Water Penetration Structual Test
Performance Test Pressure Infiltration/ Resistance Test Design Pressure Pressure building code required design pressures. Structural test pressures, which are tested at Three-Panel, PG Upgrade (80, 100) Dual-Pane Class LC-PG50 Size Tested 141" x 119" 50/50 † † < 0.2
Grade Exfiltration Rate Pressure
1.5 times the design pressure, should not be used for determining design pressure code
R LC Pa psf L/s·m 2 cfm/ft 2 Pa psf Pa psf Pa psf compliance. In the example above, a PG 50 performance grade rating, which passes a Three-Panel, PG Upgrade (80) Dual-Pane Class LC-PG50 Size Tested 141" x 199" 50/50 † † < 0.2
15 - 75 1.57 1.5 0.30 140 2.92 720 15.04 1080 22.56 Four-Panel (611) Dual-Pane Class LC-PG50 Size Tested 189" x 82" 50/50 † † < 0.2
20 - 75 1.57 1.5 0.30 150 3.13 960 20.05 1440 30.08 50 psf design pressure, should be used for determining code compliance, not the structural
25 25 75 1.57 1.5 0.30 180 3.76 1200 25.06 1800 37.59 test pressure of 75 psf. Four-Panel, PG Upgrade (611) Dual-Pane Class LC-PG65 Size Tested 189" x 82" 65/70 † † < 0.2
30 30 75 1.57 1.5 0.30 220 4.59 1440 30.08 2160 45.11
35 35 75 1.57 1.5 0.30 260 5.43 1680 35.09 2520 52.63 If you need further details about how Andersen® products perform to this standard, Four-Panel (80, 100) Dual-Pane Class LC-PG40 Size Tested 189" x 119" 40/40 † † < 0.2
40 40 75 1.57 1.5 0.30 290 6.06 1920 40.10 2880 60.15 Four-Panel, PG Upgrade (80, 100) Dual-Pane Class LC-PG50 Size Tested 189" x 119" 50/50 † † < 0.2
45 45 75 1.57 1.5 0.30 330 6.89 2160 45.11 3240 67.67 contact your Andersen supplier.
50 50 75 1.57 1.5 0.30 360 7.52 2400 50.13 3600 75.19 Frenchwood ® Hinged Inswing Patio Door
55 55 75 1.57 1.5 0.30 400 8.35 2640 55.14 3960 82.71 If you need further information about the AAMA/WDMA/CSA 101/I.S.2/A440-11 standard
60 60 75 1.57 1.5 0.30 440 9.19 2880 60.15 4320 90.23 or the Hallmark Certification Program please contact: WDMA, 330 N. Wabash Avenue Single Stationary (611, 80, 100) Dual-Pane Class LC-PG45 Size Tested 38" x 119" 45/55 30 26 < 0.2
65 65 75 1.57 1.5 0.30 470 9.82 3120 65.16 4680 97.74
70 70 75 1.57 1.5 0.30 510 10.65 3360 70.18 5040 105.26 Suite 2000, Chicago, IL 60611 Phone: 312-321-6802 Web: wdma.com Single Stationary, PG Upgrade (611) Dual-Pane Class LC-PG65 Size Tested 38" x 82" 65/80 30 26 < 0.2
75 75 75 1.57 1.5 0.30 540 11.28 3600 75.19 5400 112.78 Where designated, Andersen products are tested, certified and labeled to the requirements Single Stationary, PG Upgrade (80, 100) Dual-Pane Class LC-PG65 Size Tested 38" x 119" 65/70 30 26 < 0.2
80 80 75 1.57 1.5 0.30 580 12.11 3840 80.20 5760 120.30
85 85 75 1.57 1.5 0.30 580 12.11 4080 85.21 6120 127.82 of the Hallmark Certification Program. Actual performance may vary based on variations • "Performance Grade (PG)" ratings may vary from tested performance rating for larger or smaller units of a particular type.
90 90 75 1.57 1.5 0.30 580 12.11 4320 90.23 6480 135.34 in manufacturing, shipping, installation, environmental conditions and conditions of use. • "Sound Transmission Class (STC)" & "Outdoor/Indoor Transmission Class (OITC)" ratings are for individual units based on independent tests and represent entire unit. continued on next page
95 95 75 1.57 1.5 0.30 580 12.11 4560 95.24 6840 142.86 • This data is accurate as of January 2018. Due to ongoing product changes, updated test results, or new industry standards, this data may change over time.
100 100 75 1.57 1.5 0.30 580 12.11 4800 100.25 7200 150.38 • Where designated, Andersen products are certified and labeled to the requirements of the Hallmark Certification Program. Actual performance may vary based on variations in manufacturing, shipping, installation, Combination Designs, Product Performance
environmental conditions and conditions of use.
• Contact your Andersen supplier for more information. & Installation
†Data not available.
219